SPECIFICATIONS FOR FOR K2N SERIES, GENERATOR KITS, FOR O.E.M. COMPLETE GENERATOR SET ASSEMBLY

 
GENERATOR MODELS K2N-30 K2N-40 K2N-50 K2N-75 K2N-90 K2N-100 K2N-125 K2N-140
VOLTAGE REGULATION ±5% VOLTAGE REGULATION FROM NAME PLATE RATING
"KLEEN-POWER" WAVEFORM HARMONIC DISTORTION IS LIMITED TO JUST 7%
CODE G ELECTRIC MOTOR START POWER IN, HP 1/2 HP 1 HP 1.5 HP 2 HP 2.5 HP 3 HP 3 HP 5 HP
ENGINE HP @ 3600 RPM REQUIRED TO ACHEIVE MAX KW POWER 5.5 HP 6.5 HP 9 HP 14 HP 16 HP 18 HP 22 HP 25 HP
IF ENGINE HORSEPOWER IS REDUCED, THE GENERATOR KW RATING IS REDUCED IN DIRECT PROPORTION
HEAVY DUTY BALL BEARING BALL BEARING ROTOR SUPPORT ON ALL MODELS
WINDING INSULATION SYSTEM CLASS H, 200 DEG. CELSIUS SLOT INSULATION, VARNISH, AND COPPER WINDINGS
LENGTH,  INCHES 9-1/2 9-1/2 11-5/8 13-1/8 13 13 13 16
WIDTH (DIA.), INCHES 9 9 9 9 9 9 9 9
HEIGHT, INCHES 9-1/8 9-1/8 9-1/8 9-1/8 9-1/8 9-1/8 9-1/8 9-1/8
NET WEIGHT, LBS. 53 57 73 81 93 102 109 125
SHIP WEIGHT, LBS. 63 67 83 91 103 112 119 135
 

SPECIFICATIONS FOR FOR K4N SERIES, GENERATOR KITS, FOR O.E.M. COMPLETE GENERATOR SET ASSEMBLY

 
GENERATOR MODELS K4N-190 K4N-250 K4N-300 K4N-450 K4N-550 K4N-650 K4N-800 K4N-1050 K4N-1250
VOLTAGE REGULATION SOLID STATE VOLTAGE REGULATOR WITH ±1/2% VOLTAGE DRIFT PER 40°C TEMP. CHANGE 
"KLEEN-POWER" WAVEFORM HARMONIC DISTORTION IS LIMITED TO JUST 3-4%
CODE G ELECTRIC MOTOR START POWER IN, HP 7-1/2 HP 12 HP 15 HP 25 HP 30 HP 35 HP 40 HP 50 HP 60 HP
ENGINE HP @ 3600 RPM REQUIRED TO ACHEIVE MAX KW POWER 28 HP 37 HP 45 HP 67 HP 82 HP 98 HP 120 HP 156 HP 190 HP
IF ENGINE HORSEPOWER IS REDUCED, THE GENERATOR KW RATING IS REDUCED IN DIRECT PROPORTION
HEAVY DUTY BALL BEARING BALL BEARING ROTOR SUPPORT ON ALL MODELS
WINDING INSULATION SYSTEM CLASS H, 200 DEG. CELSIUS SLOT INSULATION, VARNISH, AND COPPER WINDINGS
NET WEIGHT, LBS. 250 279 349 513 578 626 779 929 1070
SHIP WEIGHT, LBS. 275 304 374 548 613 661 824 974 1120
 
Gillette Generators, Inc.
Copyright © 2004  All rights reserved.