MODELS ATS-104
THRU ATS-800, SERIES 300, 1 PH, 240V. ; AND 3 PH 208, 240, 480, & 220 VAC, NEMA-1 AND NEMA-3R ENCLOSURES FOR LARGE KW INSTALLATIONS |
|
Install these automatic transfer
switches into new or existing factories or large business's, using GILLETTE'S
SENTRY-PRO large kw gen-sets up to 200 kw.
 |
|

SERIES 300 MICROPROCESSOR
CONTROL PANEL |
|

DOOR MOUNTED CONTROL
& DISPLAY PANEL
|
|
|
SERIES 300 ATS RATED 400
AMPERES |
|
Shown above is design of heavy duty transfer
switches from 104 amps -1200 amps in NEMA-1 enclosure. NEMA-3R enclosures
for outdoor installation is also available. The included microprocessor
performs many automatic engine functions and control procedures.
OPERATION
These heavy duty SERIES 300,
industrial/commercial rated ATS systems includes
suitable voltage sensing circuitry for automatic transfer of an "all
class" electric load, to an emergency power, standby generator set, in
the event of a drop or total loss of utility power. Upon restoration of
utility power, the electric load is automatically re-transferred back to
utility power.
ASCO
SERIES 300 HEAVY DUTY
AUTOMATIC TRANSFER SWITCH FEATURES
-
30 AMPS TO 1200
AMPS in compact design.
-
AVAILABLE TO 600 VOLTS IN SINGLE OR THREE
PHASE.
-
TRUE DOUBLE-THROW, INHERENTLY INTERLOCKED CONSTRUCTION (NO
INTENTIONAL OFF POSITION).
-
MECHANICALLY HELD - ELECTRICALLY
OPERATED USING THE PROVEN DESIGN OF A SINGLE SOLENOID OPERATOR.
THIS DESIGN ELIMINATES ELECTRIC VIBRATION NOISE ON SOLENOID OPERATING
POSITION.
-
CONTACTS ACCESSIBLE FOR EASY
INSPECTION AND PREVENTIVE MAINTENANCE.
-
SUPPLIED WITH SOLID NEUTRAL TERMINATION.
-
UL1008
LISTED FOR TOTAL SYSTEMS LOADS (INCLUDING INDUCTION MOTOR LOADS).
-
MEETS NATIONAL ELECTRICAL CODE ARTICLES 700, 701, AND 702, PLUS CSA
REQUIREMENTS. GENERAL PURPOSE TYPE 1 (FOR INSIDE INSTALLATIONS)
AND TYPE 3R (FOR OUTSIDE INSTALLATIONS) ARE AVAILABLE THROUGH 1600
AMPS. NOTE ADD SUFFIX -3R TO ALL TRANSFER SWITCH MODELS FOR NEMA
3R ENCLOSURES.
-
MANUAL TEST SWITCH.
-
TIME DELAY BYPASS
SWITCH.
-
TIME DELAYS :
ADJUSTABLE TIME DELAY TO OVERRIDE MOMENTARY NORMAL SOURCE OUTAGES;
ADJUSTABLE TRANSFER DELAY TO EMERGENCY POWER; ADJUSTABLE RETRANSFER TO
NORMAL UTILITY POWER; 5 MINUTE UNLOADED RUN TIME FOR ENGINE COOLDOWN.
-
SWITCH POSITION LIGHTS.
-
ADJUSTABLE CLOSE
DIFFERENTIAL VOLTAGE SENSING ON ALL PHASES OF UTILITY POWER.
PICK-UP VOLTAGE IS ADJUSTABLE TO 95% OF NOMINAL VOLTAGE; DROP-OUT VOLTAGE IS
ADJUSTABLE FROM 70% TO 90% OF NOMINAL VOLTAGE.
-
SELECTIVE LOAD
DISCONNECT WITH DOUBLE-THROW CONTACT TO RATE AT AN ADJUSTABLE 0-20
SECOND TIME DELAY PRIOR TO TRANSFER AND RESET 0-20 SECONDS AFTER
TRANSFER.
-
IN PHASE MONITOR TO TRANSFER MOTOR LOADS WITHOUT ANY
INTENTIONAL OFF TIME, TO PREVENT IN RUSH CURRENTS FROM EXCEEDING NORMAL
STARTING LEVELS.
-
ENGINE EXERCISOR TO AUTOMATICALLY TEST ENGINE
EACH WEEK. THIS INCLUDES CONTROL SWITCH TO TEST WITH OR WITHOUT
LOAD.
Dimensions and Shipping
Weights
UL Type 1 Enclosure (See notes below for
information on Type 3R, 4 & 12 Enclosures)
| SWITCH
RATING AMPS |
|
PHASE
POLES |
NEUTRAL
CODE |
DIMENSIONS,
IN. (MM)3 |
APPROX.
SHIPPING WEIGHT LB. (KG)3 |
| WIDTH |
HEIGHT |
DEPTH |
| 104 |
2 |
-- |
17-1/2 (445) |
31 (787) |
11-5/8 (295) |
67 (31) |
| 2 |
B |
17-1/2 (445) |
31 (787) |
11-5/8 (295) |
70 (32) |
| 3 |
-- |
17-1/2 (445) |
31 (787) |
11-5/8 (295) |
70 (32) |
| 3 |
B |
17-1/2 (445) |
31 (787) |
11-5/8 (295) |
73 (33) |
|
|
| 150,
200 |
2 |
-- |
17-1/2 (445) |
31 (787) |
11-5/8 (295) |
69 (32) |
| 2 |
B |
17-1/2 (445) |
31 (787) |
11-5/8 (295) |
72 (33) |
| 3 |
-- |
17-1/2 (445) |
31 (787) |
11-5/8 (295) |
72 (33) |
| 3 |
B |
17-1/2 (445) |
31 (787) |
11-5/8 (295) |
75 (34) |
|
|
| 230,
260, 400 |
2 |
-- |
18 (457) |
48 (1219) |
13 (330) |
117 (53) |
| 2 |
C |
18 (457) |
48 (1219) |
13 (330) |
125 (57) |
| 3 |
-- |
18 (457) |
48 (1219) |
13 (330) |
125 (57) |
| 3 |
C |
18 (457) |
48 (1219) |
13 (330) |
133 (61) |
|
|
| 600,
800 |
2 |
-- |
24 (610) |
63 (1600) |
17-1/2 (445) |
250 (114) |
| 2 |
B |
24 (610) |
63 (1600) |
17-1/2 (445) |
260 (118) |
| 3 |
-- |
24 (610) |
63 (1600) |
17-1/2 (445) |
260 (118) |
| 3 |
B |
30 (762) |
63 (1600) |
17-1/2 (445) |
320 (145) |
|
|
| 1000,1200 |
2 |
-- |
38 (965) |
87 (2210) |
24 (610) |
870 (395) |
| 2 |
B |
38 (965) |
87 (2210) |
24 (610) |
920 (417) |
| 3 |
-- |
38 (965) |
87 (2210) |
24 (610) |
920 (417) |
| 3 |
B |
38 (965) |
87 (2210) |
24 (610) |
970 (440) |
Notes:
1. For Type 3R, 4 & 12 dimensions, add the following
values to the Type 1 dimensions:
a) 104, 150, 200a - add
1.5 in. (38 mm) to the height.
b) 1000-1600A - add 3 in. (76
mm) to the height and 10 in. (253 mm) to the width.
2. For Type 3R, 4 & 12 weights, add the following values to the Type 1
weights:
a) 104, 150, 200A - add
15 lbs. (6 kg).
b) 230, 260, 400A - add 30 lbs
(14
kg).
c)
600, 800A - add 42 lbs (19 kg).
d) 1000-1600A - add 60 lbs (27
kg).
3. When temperatures below 32°F can be experienced, special precautions
should be taken, such as the inclusion of space heaters, to prevent condensation
and freezing of this condensation. This is particularly important when
environmental enclosures (Type 3R, 4 & 12) are ordered for installation
outdoors.